Aalborg Universitet

CLIMA 2016 - proceedings of the 12th REHVA World Congress volume 5

Heiselberg, Per Kvols

Publication date:

2016

Document Version

Publisher's PDF, also known as Version of record Link to publication from Aalborg University

Citation for published version (APA):

Heiselberg, P. K. (Ed.) (2016). CLIMA 2016 - proceedings of the 12th REHVA World Congress: volume 5.

Department of Civil Engineering, Aalborg University.

General rights

Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights.

- Users may download and print one copy of any publication from the public portal for the purpose of private study or research.

- You may not further distribute the material or use it for any profit-making activity or commercial gain - You may freely distribute the URL identifying the publication in the public portal -

Take down policy

If you believe that this document breaches copyright please contact us at vbn@aub.aau.dk providing details, and we will remove access to the work immediately and investigate your claim.

Downloaded from vbn.aau.dk on: September 14, 2022

(2)

Wind Driven-ventilation Enhancement Strategy in Low-Rise Traditional Turkish Houses

Yusuf Cihat Aydin#1, Parham A. Mirzaei#2

#Architecture and Built Environment Department, The University of Nottingham University Park, Nottingham, NG7 2RD, UK

1laxycay@nottingham.ac.uk

2Parham.Mirzaei_Ahranjani@ nottingham.ac.uk

Abstract

Currently, residential buildings are responsible for 40% of the global energy demand while 82% of this energy is produced by non-renewable sources, which significantly increase CO2 emission and global warming. Aligned with achieving the CO2 emission reduction in the near future, the role of implementation of energy- saving techniques in minimizing the mentioned energy demands are found to be more vital than at any time. As practical and economic options, natural ventilation via windows, has a huge potential to reduce buildings cooling load. The great potential of the historical designs in the reduction of dwellings’ energy demand is often underestimated in modern building construction. This study aims to assess the applicability and functionality of a common historical Turkish architectural element called “Cumba” in the improvement of wind-driven ventilation in buildings. A case study building was selected as a result of a survey over 111 different existing traditional samples across Turkey. Buildings with and without Cumbas were compared in different scenarios by development of a validated CFD microclimate model. The results of a series of simulations clearly demonstrate that Cumba can enhance the room’s ventilation rate more than two times and a smart window opening strategy can also help to enhance the mean ventilation rate by 276%. Air velocity and ventilation rate could be adjusted to a broad range of values with the existence of Cumba.

Keywords - Wind-driven ventilation; Traditional Turkish Architecture; Cumba;

Computational fluid dynamics (CFD) 1. Introduction

The average global temperature anomaly has risen by 0.68oC since the 1880s [1], and with current rates of global warming the mean global surface temperature is expected to increase by 3-5oC in the long term compared to its preindustrial level [2]. The number of climatic-related natural catastrophes has almost tripled since 1980’s, as a consequence of global warming [3]. The death of approximately 50,000 people in 2003 August heat wave in Europe can be presented as a tragic example [4]. Currently, residential buildings are

(3)

responsible for 40% of the global energy demand, and 82% of this energy is produced by non-renewable sources [5]. Furthermore, the rapidly increasing global population and global economic growth are projected to raise global energy demand by 61% by 2050 [6].Therefore, considerable energy reduction is crucial to decrease the global energy demand. For example, Europe set a goal in 20% energy demand reduction at building sector by 2020 [7].

Current investigations acknowledge the functionality of passive strategies in providing thermal comfort while being energy efficient [8].

There have been numerous highly effective natural ventilation techniques in architectural history. For example, wind-catchers (Bâdgir) have been used as an evaporative ventilation and cooling system in Persian architecture for past three thousand years. Particularly, wind-driven ventilation, mainly via windows, demonstrates a huge potential to improve Indoor air quality (IAQ) and to reduce cooling load of buildings [9]. Cumbas (Fig. 1) are a popular traditional architectural element from the Ottoman period that remains widespread in Turkish dwellings. This study thus aims to investigate the role of Cumbas in wind-driven ventilation in low-rise dwellings. For this purpose, a preliminary study among 111 different traditional Turkish houses was first conducted to identify the features of the typical Cumba and its plan typology, as a base case scenario. A 3D microclimate CFD model of the selected building was then developed to assess the potential of wind-driven ventilation using 24 different scenarios, including various wind directions, velocities and window opening configurations.

2. Description and Slection of Cumba and Benchmark Building As shown in Fig. 1, the Cumba can be identified as an extension of rooms in the first or upper floors, covered by windows on one to four different facades (Fig. 1c). A Turkish house plan consists of rooms aligned around the Sofa (common hall area), which is the main distinctive element that creates dwellings characteristics. Moreover, the typical configurations of houses mean that is easy to estimate the dwelling layout from a view of the exterior based on patterns of building development from the interior to the exterior borders (See Fig. 1b).

According to the conducted survey, the majority of 111 sample buildings are located in Istanbul and have four rooms. The area of the main and smallest rooms varies between 11-20m2 and 21-30m2, respectively.

Their windows’ widths range from 0.6m to 1m, with the most common being about 0.8m. 82% of the sample buildings contain an average of two Cumbas in their design, and about 75.8% of the Cumba typologies are three-sided (Fig. 1c). The original and modified layouts of this building are illustrated in Fig. 2. The north-west Cumba was modified by adding two 0.8m-wide windows on the eastern and western façades. The wall between

(4)

the northeast and northwest rooms was extended, as indicated by dots in Fig. 2b. The roof shape was also assumed to be flat, in order to simplify the construction of 3D mesh of the microclimate CFD model (Fig. 2b). The area of the northwest room was kept the same (16m2) in all scenarios.

Fig. Fejl! Ingen tekst med den anførte typografi i dokumentet.. (a) Cumba and traditional Turkish house components [10], (b) traditional Turkish house [11], (c) most common types of Cumba (x: three-sided, y: four-sided, z:one-sided Cumba), (d) typical traditional Turkish interior

room and Cumba [11]

Fig. 2. (a) original layout [12] and Cumba modification of the selected building, (b) simplified benchmark building layout with and without Cumba

3. Methodology

As summarized in Table 1, the wind-driven ventilation effect of Cumbas was studied under three main conditions in 24 scenarios, including

(5)

five different wind directions from north, northwest, northeast, west and east; four different wind velocities of 1.7m/s, 3.3m/s, 4.7m/s, and 5.5m/s (S1-S20); and four different window opening configuration scenarios (S21- S24). Wind velocities and directions were inserted to the model according to the monthly average statistics of Istanbul for the last 18 years. The recorded monthly wind velocity shows a minimum of 1.7m/s [13], a maximum of 5.5m/s and an average of 4.7m/s. Moreover, 3.3 m/s wind velocity was simulated as an additional scenario to cover a spectrum of velocities between minimum and maximum values.

Table 1. Summary of case study scenarios for 48 CFD simulations

Scenario

With and without integration of Cumba Wind directions

North East West Northeast Northwest Wind

velocity (m/s)

1.7 S1 S2 S3 S4 S5

3.3 S6 S7 S8 S9 S10

4.7 S11 S12 S13 S14 S15

5.5 S16 S17 S18 S19 S20

Scenario (Opened windows)

Under prevailing wind (Northward) and average wind velocity (4.7m/s) conditions Window

opening combination

S21 W1 - W2 - W3 - W4 - W5 - W6

S22 W2 - W3 - W4 - W5

S23 W2 - W3 - W4 - W5 - W6

S24 W1 - W2 - W3 - W4 - W5

Computational Fluid Dynamics (CFD) with 3D RNG k–ε turbulence model and structured non-uniform mesh with 2.8 million cells was utilized in this study (Fig. 3c and 3d). As shown in Fig. 3, the CFD model is a two- storey building with a storey height of 3m (6m in total). The ground floor was assumed to be 17m × 8.5m × 3m (length × width × height), and the first floor had same dimensions as the ground floor with 1m extension of two Cumbas on the north (Fig. 3a). Mean indoor air speed and ventilation rate were only simulated in the modified northwest room with a three-sided Cumba; the northwest room door was assumed to be closed and the other rooms and the Sofa were not included in the simulations. As shown in Fig.

3b, the dimension of the northwest room is 4.5m × 4.5m × 3m (length × width × height), including 0.25m wall thickness. The north façade of the integrated Cumba has four 0.8m × 1m (width × height) windows, whereas the east and west façades have only one window each. All windows are located at 4.5m height from the floor, and were assumed to be opened in simulations scenarios of S1 through S21.

(6)

( c ) ( d )

Fig. 3. (a) 3D CFD domain model (b) locations of the measured velocities in bechmark room (c and d) generated meshes

The recommended CFD domain boundaries size were set to be 98.5m × 77m × 36m as depicted in Fig. 3a. Microclimate CFD domain size was also expanded according to the five different wind directions to ensure sufficient distance between boundaries and the isolated building [14]. The inflow, outflow and symmetry boundary conditions were respectively associated to the inlet, outlet and lateral walls of the study domain to replicate appropriate boundary conditions [15,16]. Moreover, the boundary surfaces of the Turkish house model were defined as walls, with no slip condition for the surfaces.

Fig. 4. Validation outcomes for window W5 and W2

(7)

The results of the CFD simulation were compared with [17], to validate the developed model. The velocity in the studied windows is in a fair agreement with the CFD simulation conducted by Bangalee et al. (2012);

the obtained average discrepancy is about 5.9%, which represents a similar trend as the results of [17] simulated at the centerline of the windows (Fig.

4). The validated microclimate CFD model is used in further scenarios of this study with the addition of four more windows, W1, W3, W4 and W6, to the studied room.

Existing studies noted the major limitation of wind-driven natural ventilation, which are the unpredictable variations of wind in terms of direction and speed [18]. The CFD results indicate that Cumbas can effectively harvest wind approaching from different directions and speeds (S1-S20) to improve the mean indoor air velocity and ventilation rate of the studied room. The wind-driven ventilation contribution of Cumba evaluated according to average indoor air velocity and ventilation rate comparison between building with and without Cumba. Ventilation rate is defined with the most widely used method called orifice equation as below [18]:

Q= CdA√2∆𝑃 𝑝 . (1) where Q is the ventilation rate (m3/s), Cd is the discharge coefficient (0.60- 0.65 for sharp-edged openings) [19], A is the opening area (m2), 𝜌 is the air density and P is the difference of the external and internal pressures (Pa).

4. Results and discussion

The comparison of the room mean air velocity according to different wind directions and velocities is shown in Fig. 5. The threshold of an indoor air velocity to satisfy the comfort level is also shown with a black circle in Fig. 5. This indicates that the air speeds inside the circle are assumed inadequate to satisfy occupant’s comfort. On the other hand, indoor air velocities between 0.5m/s and 1.0m/s and between 1.0m/s and 1.7m/s can be respectively defined as ideal and pleasant breeze for occupants [20].

Eventually, the speed above 1.7 m/s is defined as unpleasant. Indoor air velocity above the comfortable range is not observed in any scenarios (S1- S20). In the majority of the scenarios, indoor air velocity was observed to be below 1.0 m/s, excluding S11-S16 against the north wind. In contrast, for all non-Cumba scenarios (S1-S20), indoor air velocity is almost obtained to be below the comfortable range except for two scenarios (S15-S20).

In general, the existence of a Cumba significantly increases the indoor mean air velocity by 138% in scenarios S1-S20, with north-south wind velocity increasing by 223%, east-west by 197%, and west-east by 99%.

These wind directions also provide better performance in terms of mean indoor air velocity compared to the north-east (94%) and north-west (76%)

(8)

wind directions, mainly due to the lower pressure difference between indoor and outdoor spaces in angular wind directions (north-east and north-west).

Fig. 5 Room mean air velocity (a) 5.5m/s (b) 4.7 m/s (c) 3.1 m/s (b) 1.7 m/s

Fig. 6 Ventilation rate (a) 5.5m/s (b) 4.7 m/s (c) 3.1 m/s (b) 1.7 m/s

(9)

Fig. 7. Velocity contours of the scenarios with and without Cumba under different wind directions

(10)

Similarly, it can be observed in Fig. 6 that the existence of Cumba significantly increases the overall ventilation rate by about 224% in all scenarios, showing its potential flexibility to harvest wind approaching from different directions and velocities (See Fig. 7).

As depicted in Fig. 8, the impact of window opening configuration of Cumba was affected by where the Cumba was integrated in the building (S21-S24). It can be seen that the existence of a Cumba can significantly improve the mean indoor air velocity and ventilation rate. In comparison to S11, the minimum mean air velocity and ventilation rate difference of about 23% and 35% can be calculated when W6 is set to be closed (S25). On the other hand, the maximum mean air velocity difference is observed between scenarios S11, S21 and S23, where mean air velocity in scenarios S11 and S21 are almost equal. A maximum ventilation rate difference of about 580%

was obtained between scenarios S11 and S22. The mean air velocity and ventilation rate are elevated by about 38% and 580% in comparison to S11, when a Cumba is not integrated to the building, although they both have a similar number of windows. This clearly indicates that the enhanced wind- driven ventilation by Cumba is not only associated with windows’

orientation, but their opening configuration can also help to control and adjust different required ventilation rates.

Fig. 8. Comparison of room average air velocity and ventilation rate according to different window opening combinations

5. Conclusion

Mean indoor air velocity and ventilation rate were utilized as key indices to evaluate the wind-driven ventilation of the selected benchmark building. Various scenarios were investigated by the alteration of parameters

(11)

such as wind direction, wind velocity and window opening configuration. In general, three-sided Cumba demonstrated the most promising performance to harvest approaching wind. The Cumba could enhance the room’s mean air velocity and ventilation rate under different climatic conditions by about 1.4 and 2.2 times, respectively. The room’s mean air velocity and ventilation rate could be also adjusted to a broad range of values by the implementation of various window opening configurations.

Acknowledgement

The authors would like to express their gratitude to the University of Nottingham, and Mehmet Aydin for the financial support.

References

[1] NASA/GCC, «NASA Global Climate Change Cital Signs of the Planet,» 1 1 2016.

[Online]. Available: http://climate.nasa.gov/vital-signs/global-temperature/.

[2] IPPC/CC, «Climate Change 2014 Synthesis report Summary for polcymakes Report of the Intergovermental Panel on Climate Change,» IPPC, 2014.

[3] UNISDR, «The United Nations Office for Disaster Risk Reduction,» 1 6 2012. [Online].

Available: http://www.preventionweb.net/files/20120613_ClimateDisaster1980-2011.pdf.

[4] P. A. Mirzaei Recent challenges in modeling of urban heat island. Sustainable Cities and Society. 19 (2015) 200–206.

[5] WEC/WERS, «World Energy Council World Energy Resources 2013 Survey Summary,»

World energy Council, London, 2013.

[6] W. E. WEC/WES-2050, «World Energy Council World Energy Scenarios Composing energy futures to 2050,» World Energy Council, London, 2013.

[7] SETIS, «European Commission Energy Performance of Buildings,» 1 1 2016. [Online].

Available:https://setis.ec.europa.eu/system/files/Technology_Information_Sheet_Energy_Perfor mance_of_Buildings.pdf

[8] D. L. Samuel and S. S. Nagendra. Passive alternatives to mechanical air conditioning of building: A review. Building and Environment. 66 (2013) 54-64.

[9] F. C. McQuiston, J. D. Parker ve J. D. Spitler, Heating, Ventilating and Air Conditioning Analysis and Design; 6 edition, USA: John Wiley & Sons, Inc., 2005.

[10] C. Arseven, Sanat ansiklopedisi, 5th ed., Istanbul: Milli egitim bakanlıgı, 1983.

[11] Ö. Küçükerman, Turkish house in search of spatial identity, Turkey: Türkiye Turing ve Otomobil Kurumu, 2007.

[12] H. Talya, Gelenksel Turk mimarisinde yapı sistem ve elemanları, Istanbul: Turkiye Anıt Cevre Turizm Degerlerini Koruma Vakfı (TAC) , 2007.

[13] WB, «Weatherbase,» 1 1 2016. [Online]. Available: http://www.weatherbase.com/.

[14] P. A. Mirzaei and J. Carmeliet. Dynamical Computational Fluid Dynamics Modeling of the Stochastic Wind for Application of Urban Studies. Building & Environment, 70 (2013) 161-170.

[15] P. A. Mirzaei and M. Rad. Toward design and fabrication of wind-driven vehicles:

procedure to optimize the threshold of driving forces. Applied Mathematical Modeling. 37 (2013) 50–61.

[16] P.A. Mirzaei and F. Haghighat. Pollution removal effectiveness of the pedestrian ventilation system. Journal of Wind Engineering & Industrial Aerodynamics, 99 (2011) 46–58.

[17] M. Bangalee, S. Lin and J. Miau. Wind driven natural ventilation through multiple windows of a building: A computational approach. Energy and Buildings. 45 (2012) 317–325.

[18] C.-R. Chu and B.-F. Chiang. Wind-driven cross ventilation in long buildings. Building and Environment. 80 (2014) 150-158.

[19] H. B. Awbi, Ventilation of Buildings, 2nd ed., New York: Taylor & Francis, 2005.

[20] ECOTECT, «Naturalfrequency,» 29 01 2016. [Online]. Available:

http://wiki.naturalfrequency.com/wiki/Air_Movement.

Referencer

RELATEREDE DOKUMENTER

The Danish Parliament must continue to ensure that the objectives of the Folkeskole remain clear and make sure that the local authorities accept the re- sponsibility for operating

One of the critical tasks of the International Energy Agency’s Energy Conservation in Buildings and Communities Program’s (IEC ECBC’s) Annex 61 “Business and Technical Concepts

Simulation was carried out within the framework of Annex 61 “Business and Technical Concepts for Deep Energy Retrofit of Public Buildings” of program “Energy

• To the reach these goal the case studies have been analysed to create an overview of what energy measures have been implemented, the obtained energy savings, the reasons for and

Product innovation includes prefabricated innovative, modular composed building envelope elements, including the integration of multifunctional components for climate control,

The two calculations corresponding to Be10 with qualified parameters and PHPP with qualified parameters provide reasonably similar results for district heating consumption before

The aim of the research is to highlight the problem of overheating in energy renovated single-family houses in Denmark and to investigate the ability of a

3 shows the COP (as ratio of thermal performance on the condenser divided by the power consumption of the compressor) of both micro-heat pumps depending on the ambient air